Cerberus PRO Interactive - FC722-ZE
PRODUCTS

Cerberus PRO Interactive – FC722-ZE

PROJECT
OFFER
GET !

    GET A PROJECT OFFER

    You can fill out our form to get a project proposal.

    fire detection

    The advantages of technology come to the fore in order to survive fires that can cause serious damage, loss of life and property with minimum damage. Nowadays, it can be very difficult to be aware of the fires that may occur due to the widespread use of multi-storey buildings. Because fires can start in unused areas as well as living areas. In order to be protected from fire, fire detection technologies draw attention. This system, which analyzes gas and smoke with special sensors, can warn every person in the building in case of fire. These technologies can be used in many areas such as homes, hospitals, schools and workplaces.

    Fire Detection Systems

    Fire detection technologies, which give the first chance to respond to the fire and extinguish it before it grows, add value to human life. It provides a safe environment and attracts everyone's attention with its easy use. The system, which is used together with the fire alarm unit, is supported by different equipment. It basically consists of various alarm detectors, flashers and buttons.

    The fire detection system sends the information it receives via cable connections to the main panel. It is transmitted to the control panel by exchanging information between the detector and the system cable. Ceiling mounted heat and temperature rise detectors give a warning with audible alarms in case of a leak. Users can monitor the received information from the panel. It should be applied to an area of ​​sufficient width to get the best efficiency from the system.

    FIRE DETECTION SYSTEMS
    Read More
    Cerberus PRO Interactive – FC722-ZE
    FC722-ZE
    Product Features

    The FC722-ZE (2-loop, expandable to 4) is a compact fire control panel with an integrated operating unit that can process signals from Cerberus™ PRO devices up to 252 addresses.

    The fire control panel can be used as a standalone version or networked.

    It can be programmed with a user-friendly Cerberus-Engineering-Tool to create a versatile system.

    Up to 32 fire control panels and fire terminals can be connected to a single cluster (C-WEB/SAFEDLINK network), or up to 16 panels when the cluster is connected to a hazard management system.

    Using a fiber optic backbone (C-WEB/LAN), up to 14 of these clusters can be networked with up to 16 panels each.

    This topology enables the creation of an EN 54 compliant network with up to 64 fire control panels and fire terminals.

    All detector lines are monitored for earth faults.

    Customization of user text directly in the terminal or with the Cerberus-Engineering-Tool Up to 2000 events can be stored according to various criteria.
    Automatic summer/winter time change.

    Detection and auto-reading (auto-configuration) of all C-NET devices provides instant simple operation.
    Stored data can be loaded via Cerberus-Remote access.

    The FC722-ZE is ideal for medium-sized applications, eg. workshops, hotels, etc. or when networked as part of much larger applications With flexible cross-linking possibilities, the FC722-ZE can also be used for extensive systems.

    Technicial Specifications
    • Detector compatibility Cerberus PRO FD720
    • Number of addresses 252
    • Number of detector lines 2 (4) loops or 4 (8) stub lines
    • Programmable input/output 8
    • Relay outputs 1x RT alarm , 1x RT fault
    • Supervised output 1x RT alarm , 1x RT fault , 1x Horn
    • Mains voltage AC 230 V
    • Operating voltage DC 21…28.4 V
    • Operating current 5000 mA
    • Power supply 150 W
    • Bypass time for emergency power supply 72 h
    • Battery capacity 2x 12 V, 26 Ah
    • Plug-in position 2 -> for serial interfaces RS232, RS485 , 2 -> for network modules , 1 -> for loop extension (C-NET)
    • Operating temperature -8…42 °C
    • Storage temperature -20…+60 °C
    • Relative humidity ≤95 % rel. (no condensation)
    • Protection category IP30
    • Color housing/cover Light grey, ~RAL 7035 / Gray, ~RAL 050 00 00
    • Cabinet dimensions (W x H x D) 430 x 796 x 160 mm (without cover cap) 430 x 796 x 188 mm (with cover cap)
    • Accessories DL3750+ Matrix printer (Extern) , FCA1209-Z1 Output module (230 V) , FCA2014-A1 Cable kit (communication) , FHA2015-A1 Flush mounting bezel two HU , FHA2016-A1 19" mounting kit , FHA2017-A1 Flush mounting bezel one HU , FTO2005-C1 Key switch (Kaba) , FTO2006-B1 Key switch (Nordic) , Z3B171 Relay module
    • Expansion FCA2001-A1 RS232 module (isolated) , FCA2002-A1 RS485 module (isolated) , FCA2005-A1 Sounder module , FCA2031-A1 Connection module (MoNet) , FCA2033-A1 License key (S1) , FCA2034-A1 License key (S2) , FCA2035-A1 License key (S3) , FCI2001-A1 Fire brigade periphery module , FCI2003-A1 Loop extension (FDnet/C-NET) , FH7202-Z3 Housing (Standard) , FH7203-Z3 Housing (Comfort) , FHA2007-A1 Mounting plate , FHA2035-A1 Mounting kit (marine) , FN2001-A1 Network module (SAFEDLINK) , FN2006-A1 Fiber network module (SM) , FN2007-A1 Fiber network module (MM) , FN2012-A1 Ethernet Switch (modular) , FP2005-A1 Power supply kit (150 W, B) , FTO2001-A1 Event printer , NK8237.2 Modbus Gateway , VN2001-A1 Ethernet Module (electric/CAT5) , VN2002-A1 Ethernet Module (MM) , VN2003-A1 Ethernet Module (SM)