SIEMENS FC122-ZA 4-Zone Collective Control Panel
PRODUCTS

SIEMENS FC122-ZA 4-Zone Collective Control Panel

PROJECT
OFFER
GET !

    GET A PROJECT OFFER

    You can fill out our form to get a project proposal.

    Read More
    SIEMENS FC122-ZA 4-Zone Collective Control Panel
    SIEMENS FC122-ZA
    Product Features

    FC122-ZA is a conventional fire control panel with integrated operating unit for 4 zones.

    The controller is designed to be very simple to use while offering exceptional flexibility through an extensive feature list.

    The FC122-ZA is ideal for small applications, eg. in schools, shops, hotels.

    Extensions and accessories must be ordered separately.

    Technicial Specifications
    • Operating voltage DC 21…28.6 V
    • Power supply 25 W
    • Operating current Max. 0.9 A
    • Mains voltage AC 196...253 V
    • Bypass time for emergency power supply 72 h
    • Battery capacity 2x 12 V / 4 or 7 Ah
    • Relay outputs 1x dialer fault
    • Monitored output 1x sounder line , 1x dialer fire
    • Programmable inputs 2
    • Plug-in position 1
    • Zones 4
    • Conventional devices per zone Max. 32
    • Relative humidity ≤95 % rel. (no condensation)
    • Operating temperature -5…+40 °C
    • Storage temperature -20…+60 °C
    • Protection category IP30
    • Color housing/cover Gray, ~RAL 000 50 00
    • Dimensions (W x H x D) 310 x 360 x 85 mm
    • Accessories FCA1206-Z1 Key switch set (Nordic SE) , FCA1209-Z1 Output module (230 V) , FDCH221 Housing for input/output modules , AX1213 Battery (12 V, 4.5 Ah) , FA2003-A1 Battery (12 V, 7 Ah, VDS)
    • Expansion FCA1203-Z1 Output card 2M 2R , FTO1201-H1 EVAC module (NL 2&4 zones)