Read More
SIEMENS DCA1192A
Product Features
Electronic unit for DC1192 input/output module,
For connection of collective/SynoLINE600 addressable fire detectors SynoLOOP fire detection system (special detectors) or shunt Zener diode barriers, detectors for explosion-hazardous areas) or for activation of alarm devices.
The built-in isolator allows the fire control panel to localize short circuits and open lines.
With its automatic addressable feature, no dip switch or punch card setting is required.
The electronic unit is attached to the body just before commissioning.
Line termination elements are also included in the package.
Technicial Specifications
- Detection line voltage DC 18...22 V
- Operating voltage External DC 18...32 V
- Detection line current Max. 5 mA
- Operating current Control line max. 2 A, 60 W
- Quiescent current ≤45 mA